  1. davidlabbe998

    Water hammer effect on anchor

    It's not possible. As you can see in section "E-E" in attachment the discharge pipe is inside a concrete monoliths of 5.9 m wide from the wall of the lock.https://files.engineering.com/getfile.aspx?folder=b01c1e79-db41-4b1d-9eb1-92e82d05d52a&file=4200_Modifié.pdf
  2. davidlabbe998

    Water hammer effect on anchor

    Thank you for the recommendation. Here is what I've done : Velocity reduced by pipe elasticity : V reduced =(1477.8 m/s)/(1+(102mm/6mm)*(2.18*10^6 kN/m^2/207*10^6 kN/m^2))^0.5 = 1361 m/s Water Hammer pressure : DeltaP = 1000 kg/m^3*1361 m/s*(4.41-0)m/s = 6 002 kPa Water Hammer absorber...
  3. davidlabbe998

    Water hammer effect on anchor

    With this plan, you can see the general arrangment at the top (Vue agrandie "C"). I've used EPANET to get the flow/Velocity/head pressure data right.https://files.engineering.com/getfile.aspx?folder=84d379f1-de99-4dce-a026-5b0d6c8e8249&file=St-Lambert_page_2.pdf
  4. davidlabbe998

    Water hammer effect on anchor

    Hey everyone, I have an issue with a pumping system for ÉC-1, see in attachment. Yes, sorry it is in french, you might use google transl... Velocity calculated : 4.41 m/s. Steel galvanized 4" A53 B pipe Pump is Flygt NP 3153.462 What will be the water Hammer effect? Will the air chamber...