THERE ARE OTHER COOLING AFFECTS TAKING PLACE NATURAL CONVECTION AND ENCLOSURE ITSELF. THESE LASTED ABOUT 7 YEARS, ONE OF THE POWER CENTERS TRANS FORMER FINALLY FAILED DUE TO HEAT. THEY WANT US TO COME UP WITH A SOLUTION. WE ARE PULLING AIR THROUGH THE DUCTS IN THE COILS WITH THIS SETUP I AM...
Irstuff, actually i have to deal with 90Kw losses but that is not what i need i just need to calculate the static pressure the fans will be dealing with. Thanks man.
Sorry for my lack of knowledge but I have searched and searched to no avail. I am in a unique situation. I have to figure out how to cool a 4000kva transformer in a existing coal mine power center. I am going to have a tube above the coils on this transformer with holes cut out above each coil...
I am designing a tunnel boring machine power center. Ive been able to calculate ventilation for natural convection but the customer wants filters. I need to know how to combine the static pressure of the filters with the ventilation open area. Anyone know how this is done?