The fire department is asking for one Class II hose station in a warehouse. Its been awhile since I have done this and wanted some advice. This is for fire use only. Do I need to have a separate riser for the single hose valve or can I connect to the system. Im looking at 8.17.5.1.3 and .4 it...
Sorry, but to clarify they installed regular k8.0 uprights for a rack storage building. We are not working in that area but wanted some advise on what everyone else would do.
So I am doing a job that needs some office sprinklers that need to be changed out and I received the old sprinkler plans. Well, not too old about a year ago installed. I noticed on one of the hydraulic areas that the system has a .385 density and has 8.0 k factor heads? Victaulic V3401 heads to...
I want to thank you guys for replying. There are some Level 3 aerosols and looking at NFPA 30B with a ceiling height of 23' or so I would have to calculate a .60 over 2500 with a 11.2 head. They are storing at 5' in cartons on wood pallets.
Hi all! I was wondering if I could get some help on this one. Looking at a building that has some aerosols on racks up to 10'. Paints, degreaser solvents, adhesive, pvc cement (liquid can) and some HVAC flush kits. We don't get into a ton of this so just wanted some help if you dont mind. Single...
the top of deck will be 18' high and slope to 17' and the building is 25000 sq ft. Right now they will be storing all wood doors and cabinets. And I will also confirm the aisle width
So using the table it looks like I start with 0.37 over 2000 and reduce to .24 over 2000. Am I looking at this correctly? I just to make sure since it will change sprinkler head spacing
I'm try to learn a couple of things on storage. We are looking at warehouse that will have upto 16' storage of doors and windows which I am thinking it falls under class III. With that being said I flip to table 16.2.1.3.2 and with a class III nonencapsulated with 8' aisles I can provide no...