HI....
I finally found this factors in the manual...
Thank you for pointing me...
Now it's clear.
Can't believe I didn't see that.
Thanks one more time.
Thanks a lot.
This is very helpful.
Just one more thing. How come I get 226mA for 2Ph injection and 200mA for 3ph injection for HV side.
According to attached table, correction factor should be 1, but I have 226/200=1.13?
This is confusing me....
Hi again,
I hope somebody can help me with my problem which I describe earlier...
I will try to write it more detail and with easier example....
So i have differential protection relay and I would like to test pick up of differential protection, for example, for Yy0 transformer vector group.
If...
Hello,
I have one differential relay and I'am trying to test transformer differential protection.
Using current injection test set I inject currents only from side of transformer.
For example, pick up value for differential protection is 500mA (secondary value):
- I inject in all three phases...