Hello Engineers,
I am designing an embed stud connection at CMU wall- Headed studs inside wall & plate outside the wall (refer below snap & attachment).
Generally, if the wall is concrete, I would directly design in HILTI Profis suite (with plate & studs embedded inside the concrete wall)...
@Tmoose, Yes, expansion or chemical anchors didn’t work as the concrete depth is just 3” @ deck flanges. I ran the arrangement in Profis & it won’t design for due to insufficient depth (min.=4”).
@dold, You are right. Technically, I feel the cane detection rails doesn’t need to be designed for...
Hello engineers,
I have a cane detection rail post (27" height) that requires to be connected to a concrete deck slab which is 5" THK (2" deck + 3" concrete). Expansion or chemical anchor (HILTI) connection didn't work & was even rejected by the SER. So I was wondering if I could go for a...