  1. evang999

    Mixing Delta and Wye PDUs on computer room power bus

    Thank you Bill, that was very clear. I will no longer refer to DelXX. Again, much appreciated.
  2. evang999

    Mixing Delta and Wye PDUs on computer room power bus

    Thanks for that info, Bill. The aim here is to be able to use a particular PDU designed for 208v Delta (and not available in Wye). The Siemens modular power busses we're using already deliver 208v/3ph Wye. Trying to figure out how to adapt those to deliver Delta. We used to have equipment that...
  3. evang999

    Mixing Delta and Wye PDUs on computer room power bus

    We don't plan to mix wye and delta circuits - only to take a 4-wire wye circuit and make it a 208v delta by eliminating the neutral. There is a ground present. I'm told faults are handled by co-ordinated breakers: initially on the PDU itself (per phase), then at the buss drop cable to the PDU...
  4. evang999

    Mixing Delta and Wye PDUs on computer room power bus

    Power to our computer room servers is delivered on 208V/3ph/Wye overhead busses to IEC 60309 connectors on drop cables. In-cabinet Wye PDUs connect to those. To ease the transition to a new type of PDU, we plan to add more connections to the busses using an IEC 60309 Delta drop cable. All...