Thanks for the replies... Word is the overkill was to mitigate the effects of cold North Dakota winters on a starting system.
I have modeled the circuit in Multisim (National Instruments) but it is limited and won't let me see each battery - so I have to model it as one battery with 6...
Hello All, I have a situation where a legacy design has the following characteristics:
- (6) 12V lead acid batteries in series with another (6) lead acid batteries
- This 24V system provides starting function for (2) 1000hp diesel engines
- Each engine is equipped with a 75A alternator
- The...