Hi All
Thanks heaps for the answers.
Inrush current could be a good reason, We tried without the star side earth and tried to energise, then the CB does not trip ?
Few more info:
Supply MCCB is 80 A Rated, 3 pole breaker ( no realy..etc is connected, and no setting for the CB)
Transformer...
Hello,
I'm in a situation where a Delta Star Isolation Transformer is used to get 400V power from a HV Substation(Temporary construction works). Secondary star side is earthed (MEN/Neutral link). Attached a sketch on the arrangement.
The Supply side Circuit breaker (CB feeding primary side)...