Hello all!
I am trying to model soil structure interaction in ETABS for a G+9 RCC Framed Building with a single basement below ground level and Raft Foundation at the base. I am trying to employ Substructure Method for modeling of soil structure interaction and primarily basing my work on...
Below I have uploaded a screenshot of Column Flexural Design Details in ETABS based on Indian Code. I have a few questions regarding the design results and I would be grateful if somebody could clarify them to me!!
1. What is the purpose of calculating Initial Moment? How is Initial Moment...
I am designing a three-storey steel building in ETABS with roof truss. Should we assign end releases to the truss members? If so, what is the proper way to apply end releases? I see that even when end releases are not applied, and we check for axial/shear/bending moments in those truss members...
When we are designing a steel structure in ETABS, I see that we can assign lateral bracing to the main beams supported by secondary beams. Should we always assign this property to the floor beams? What is the significance of assigning this lateral bracing? How can we be assured that the...
Yes. I do have a basement modelled. I have attached here the Shear Wall Design Summary generated from ETABS. Any help would be appreciated! https://files.engineering.com/getfile.aspx?folder=5ae02683-1e42-4cbe-91b0-598a515c896f&file=Shear_Wall_Design_Report_ETABS.pdf
I am designing an 8-storey RCC building in ETABS with lift core and shear walls. While designing for Shear Wall, I get the error message as indicated in the picture attached with this post. Currently, I have defined 250 mm thick wall section. However, the wall is failing in flexure and also some...
Hello,
When analyzing a building in ETABS, deflection can be seen only for the topmost storey as shown in the picture that I have attached along with this thread. Can anybody tell me what might be the reason for this and what is the solution for...
Sorry about that. I had previously assigned diaphragms by selecting all the joints at a particular floor level. I will try by only selecting the shell elements now!
I found the problem. Seems I didn't assign diaphragms properly. When I delete the diaphragms, the behaviour of the building looks appropriate. The problem now is how do I correctly assign diaphrams to each floor level? Should we take any special care if there are shear walls??
Yes. I checked again and I think I have defined the mass source correctly.
For your reference, I will upload a screenshot of the deflected shape in 1st mode. https://files.engineering.com/getfile.aspx?folder=bd7a3a9a-eda7-4309-922f-a7da79f783dd&file=Capture.JPG
Hello,
I modelled an 8-storey building in ETABS with a Basement and Lift Core. After modeling and application of all loads, when I perform analysis I can see only the topmost storey deflecting. There doesn't seem to be any deflections in the storey below. As a result of this, the time period in...
Here it is! Deflected Shapes for first 4 modes!!https://files.engineering.com/getfile.aspx?folder=53bcb4c1-8347-4f8a-8448-200b4b7c6c44&file=Capture.JPG
I have uploaded a screenshot combining both the Codal Clause and the results in my ETABS Model!! The difference between the time periods of the first two modes is less than 10% of the higher value of time period in my model, which seems contrary to the codal requirement...
Hello!
I analyzed a fairly regular and symmetric building in ETABS and I was checking the results of Modal Analysis as per IS 1893 (Part 1): 2016. Code says that "the fundamental lateral natural periods of the building in the two principal plan directions should be away from each other by at...