  1. EE_NE

    Lightning Arrester Failures within S/S

    Thank you all for the responses, digging into it. Palletjack "For your arrestors I’m not understanding why they can’t be replaced without installing a mobile." - the ones in this scenario are bolted onto the structure, would need to de-energize the line here?
  2. EE_NE

    Lightning Arrester Failures within S/S

    RRaghunath Yes the 4.8kV is ungrounded - I will look into the neglection/delay for the operator to respond appropriately to faulty feeders. Kiribanda I will dig deeper into the detection system and see what is going on with it. The SAs on the 13.8kV side have survived thus far, field has not...
  3. EE_NE

    Lightning Arrester Failures within S/S

    Good evening, I'm a new EIT and I'm dealing with a situation and would like some thoughts/feedback involving a 13.8kV delta -4.8kV delta substation and failing lightning arresters, specifically on the low-side of the transformer and the arresters on the out-going feeder distribution. The...