  1. Netsky

    what is acceptable leakage current for power frequency voltage test?

    hi in MV switchgear/24kv in power frequency withstand voltage test -Ud:50kv for 1 min - according to IEC 60071-1 what is acceptable leakage current for power frequency voltage test? or how much should be the maximum leakage current? thanks for your help.
  2. Netsky

    power frequency test in MV switchgear

    Rated voltage values according to IEC 60071-1 (Insulation co-ordination – Part 1: Definitions, principles and rules) (see Fig. B5) Ur = rated voltage, rms value, kV. It is the maximum rms value of voltage that the equipment can withstand permanently. 24 kV rms for example. Ud = rated power...
  3. Netsky

    power frequency test in MV switchgear

    Dear che12345 Thank you very much for your attention. it was very useful for me.
  4. Netsky

    power frequency test in MV switchgear

    thanks che12345 for your help I checked out that standard (IEC 62271-1 sub-clause 2.2.1 Altitude ) And I calculated Ka factor completely acc to the full formula. it is Ka=1.02 in altitude 1200m . my test is in lab. I want to know what should I do with this Ka now ?? 1) test MV 20kv in...
  5. Netsky

    power frequency test in MV switchgear

    hi acc to IEC 62271-200 / 6.2.5 for insulated test in MV switchgear should be power frequency test voltage of 150% of the rated voltage for 1 min at an altitude of 1000 meters above sea level. that in 20kv it will be 50kv for 1 min. my question is here ,altitude of above see level in our city...