Does anyone recommend a fire protection system for a boiler feed pump? Not a code requirement, however, the facility management is asking to provide a fire protection system within its enclosure. The boiler feed pumps were enclosed for soundproofing due to the high noise produced from the...
Hi - NFPA 20 - 4.32.4.3 States that "There shall be two inspection test valves attached to the pressure sensing line that shall consist of a tee, a valve, a second tee with the branch plugged, and a second valve.[See Figure A.4.32(a)and Figure A/4/32(b)], Figure A.4.32(a) shows two inspection...