Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations KootK on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. retriever

    CT Shorted on Primary (secondary Impedance)

    if CT is connected to the dedicated analogue input of protection terminal, protection works properly, but if there is an electrical sum of some different CTs and a single relay, i suppose that differential protection can fail, because part of differential current will flow through the...
  2. retriever

    Why do you need dual ratio current transformers?

    For relay protection it is better to use higher CT ratio than for metering. Protection CT core (TPX, TPY, TPZ) has to work properly in case of short-circuit conditions. Metering core has to work properly only in case of normal load condition. In addition, if you want to choose CT to prevent...

Part and Inventory Search