Latexman, if we agitate faster, we will add more heat to the system right? Do you think it will solve this issue? Because the solution is anyway non viscous.
This is the cooling rate profile. The duty decreases as temperature decreases and probably is due to loss of thermal coefficient on the wall. However, at over 0oC we can still see that the cooling duty is quite low compared to chiller duty of 10kW.
LittleInch,
My inlet and outlet temp of the cooling circuit is almost the same. No difference which I can't say a number due to error of instruments.
I would like to keep the reaction below 5-6 oC with a coolant that will be at -20oC.
The temperature outlet with content temperature has a...
Hello,
I have a mixing tank 1.7 m3 half covered with plain cooling jacket (heat transfer area 2.44 m2).
I tend to use the mixing tank for a reaction that is exothermic (ca -10kW), for that reason I want to check if cooling duty of chiller and jacket is sufficient.
We carried out some tests...