I understand what you are saying, what if it is a thermal magnetic type?
Trying to cover all bases since I am bidding a project this week with this
combination.
Does anyone know if an existing across-the-line motor starter inside a motor control center bucket
can be changed to a 'soft-starter' without having any issues with NEC? Only wanting to change the
starter, not the breaker, control transformer, etc.
thanks
When the electric service was replaced, a backup generator and automatic transfer switch were also
installed for the pump station. It looks like the generator would be constantly running if the incoming
power was excessively unbalanced. But I didn't setup the transfer switch either.
When the drives were installed, at the same time the electric utility upgraded the service from a 480v corner grounded delta
to a 277/480v wye. Line and load reactors were installed with the drive also. Thanks for all the help!
This installation has been in service for a year now, and every month the 'electric bill'
indicates a 10% loss, now it has leveled out to around 20%. This is a rural electric
utility.
Hello,
Recently a pumping station was upgraded and the 'part-wind' starters and power factor correction capacitors for three 60hp 480 pumps were replaced with ABB ACQ580 variable frequency drives.
Ever since this upgrade, the power factor has dropped every month, dropping from 90% PF (with the...