  1. Loghman_ra

    Soft Starter for 11kV submersible pump

    Thanks Mark , Good tips, but I don't know if it is allowed to use such solution (controlled valve on discharge) in cases where ESP are used for emergency case like evacuating the floods, etc ?
  2. Loghman_ra

    Soft Starter for 11kV submersible pump

    Thanks Valvecrazy good Tip!
  3. Loghman_ra

    Soft Starter for 11kV submersible pump

    edison123 (Electrical): Yes , VFD is a solution but costly and also more consideration rather than a RVSS (no frequency change)! we are trying to find a solution based on RVSS ( no freq. change) https://vfds.com/blog/what-is-a-soft-starter/
  4. Loghman_ra

    Soft Starter for 11kV submersible pump

    Thanks Gr8blu, maybe it is better from now I use RVSS instead of SS. so we are trying to not using VFD. of course there will be bypass switch after start-up. Thanks edison123 as mentioned client asks for RVSS. Thanks waross ( yes your guess is correct, line current needs to be limited due...
  5. Loghman_ra

    Soft Starter for 11kV submersible pump

    Hello Fellows I have a case to discuss, we have a 11kV submersible motor , 1000kW. it is asked to use soft starter for starting. there is 2 limitation: 1- the submersible pump shall reach half nominal speed in less than 5 second which is due to mechanical requirement of the pump, 2- we are...