thanks for the reply sir.
for the Max pressure 50 bar is better like you said for using only Class 300 valve
I will share a drawing i got from my friend.
for the connections i need :
1 for drain
3 upside outlet for (pressure gauge, Vent, Pressure recorder hose)
2 valves for in/out
1 check...
Sir thank you for the reply .
I just need some help i can perform hydrotest i did it before the only problem is we don't have a test manifold here.
Our piping is Grooved system and according to NFPA Code the system should be tested not less the 13.8 bar our design pressure is 10 Bar.
For the...
Regards,
am a firefighting Supervisor at a power plant project and i was asked to perform hydrotest for fire fighting pipe line.
i need help with design of hydrotest manifold with the required materials for a max pressure of 60 bar.
Thanks for the help