We need to connect 33kV 630sqmm CWS cables from Power transformer(132/33kV) to switchgear. The consultant proposed solidly bonded system at first stage and then changed to bonding at single end without ECC. The distance between transformer and switchgear is 50meters and part of same earth mesh...
Hi this is my first post on eng-tips.
I have a project where I need to run 75m of 2 x circuits of 630sqmm Al cable 3 cables per phase total load of 60MVA at 22kV(STEADY STATE). At N-1 scenario one circuit needs to take 78MVA (CYCLIC LOADING). could some one guide me how to do a cyclic loading...