    6.6kV to 415 ONAN Transformer Maintenace

    Good Day jsearle, I agree with those above suggestions. you should also include the winding resistance test to ensure the same resistances between windings. For the oil analysis ,aside from Dielectric breakdown voltage test it is necessary to have laboratory test such us total acidity number...