Continue to Site

Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations GregLocock on being selected by the Eng-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. controltech

    Unbalanced current

    Well guys, as we all suspected it was definitely the power providers problem. They changed one of the transformers on the bank and everything looks good. There is minimal voltage drop and 1 amp difference in the current on the phases. I really appreciate all the input, I hope I can help someone...
  2. controltech

    Unbalanced current

    Thanks for all the feedback guys. I put in a call to the service provider and they are coming out and put a Rustrac Recorder on the service. Here are the numbers taken from the load side of the contactor except the unloaded numbers. Unloaded Voltage L1-L2 482 L1-L3 483 L2-L3 487 Loaded...
  3. controltech

    Unbalanced current

    Killing time on the internet I found this site. I have a 150 hp vertical 480 volt 3 phase motor. It is connected to a irrigation well. I have had @ 4 failures at this site. I just installed the motor after being rewound. The motor megged good and all of the lubrication points were checked. I...

Part and Inventory Search