thanks for the inputs guys.
we found out that the ground from the transformer is not connected. the genset also has a floating ground.
is this relevant?
the ground wire from the transformer is only up to the chillers' distribution panel. the chillers are grounded to each of the individual...
i need help re our chillers.
we have 3 chillers with two compressors each. funny thing is that starting last week we cant operate more than two compressors at a time with electricity coming from the utility company. we can only operate all three chillers with the standby genset power.