  1. eskim

    Paralleling Different Cable size

    Chapter 3 article 310.4 states "the paralled conductors in each phase ... shall: a)be the same length b)have the same condcutor material c)be the same size d) have the same insul type e) be terminated in the same manner" Which one is correct for the following: - Phase A =OK to have two...
  2. eskim

    Paralleling Different Cable size

    Hi, What will happen if 4/O and 240mm2 underground medium voltage 33kV cable is paralled? it's used as a part of overhead line 33kV at the beginning of the circuit. Regards, Eskim
  3. eskim

    Synchronized generator with different nominal voltage

    Hi All, Our existing generators are 11,000 V +/-5% output voltage. We set AVR 3% above nominal volt (11,350). Gens are running with voltage control set. What do you think If a new gen 10,500 V +/-5% will be synchronized with existing system. It should run 8% over its nom volt. Regards, Sumadi
  4. eskim

    Speed up motor

    Dear All, I have very basic question, but make me inconfidence regard to speeding up induction motor. The existing nameplate is 600kW, 3.3kV and 2965rpm. We have to upgrade the feed pump system by installing VSD to control this motor up to max 3400 rpm. (operating will be 3100rpm) The question...
  5. eskim

    Terminal Lugs

    Dear All, Please confirm me for this small confussion. Can I use non-insulated 600V terminal lug to be used for 11kV arrester circuit ? In my opinion Yes, since voltage will effect to insulation material only so for non-insulated doesn't matter.
  6. eskim

    3-phase Power Calculation

    Thank you all. Sorry, I am not an active member of this forum I just open this if i have problems. My calculation showed (-) sign since the angle of current are not in correct direction I think. I have to correct CT connection for this relay, and will come up eith the result next time ?
  7. eskim

    3-phase Power Calculation

    Hi, I am calculating 3-phase power with these datas, all value line-to-line: Ia= 782.831 @184.8 deg Ib= 792.247 @306.9 deg Ic= 763.033 @66.4 deg Va= 10.973 kV @0 Vb= 11.005 kV @119.9 Vc= 10.990 kV @240.1 3-phase Real Power = ??? Anybody can help me ? Thanks all.
  8. eskim

    Hi-Z on LV Overhead Line

    What does NPS (voltage/current) mean? "BTW, we had thread on the topic." What is the topic subject title..? Can I use 59G relay with input comes from broken delta PT tapped from 400V line directly? Eskim
  9. eskim

    Hi-Z on LV Overhead Line

    Dear All, Sorry if this question has been posted before, I have found 2 thread about E/F protection on D-Y transformer, but not cover my question below. 1. We have experience Hi-Z fault on LV(400V) O/H line which is supplied by 11/0.4kV Delta-Star with solid grounded pole XFMR around 50kVA. At...
  10. eskim

    Diode and Thyristor Failure in Generator Exciter

    The exciter is staked from PMG/pilot exciter --> AVR --> exciter stator --> exciter rotor --> finally to main field winding. The broken diode and thyristor is at the exciter rotor put in generator shaft, unfortunately I can't attach the drawing. In the normal running with 27MW (our Turb Gen is...
  11. eskim

    Diode and Thyristor Failure in Generator Exciter

    Dear All, I've problem above for the last two days. The six-pole, full wave rectifier have one diode and thyristor broken at the same time. We have over current and over voltage relay picked up at excitation control (V~4000V and I~40A). My question: 1. Why the current and voltage at excitation...
  12. eskim

    Oil Purifier Equipment

    Guys, I am looking for transformer oil purifier equipment will be used to purify 19000 ltrs of oil contains. Anyone could recommend Manufacturer of oil purifier, please forward ro me. Thank you all. Rgds, Eskim
  13. eskim

    AC and DC HiPot Tester

    Dear All, What is the based difference between AC and DC HiPot tester. When I test HV equipment e.g. Surge arrester, cable, generator winding, etc. What is the best method using ac or dc tester ? Some one told me that mA is the "most important" to select DC or AC ? I didn't understand what...
  14. eskim

    Surge Arrrester for Transformer

    Dear All, I am not experience in T&D. But our transformer using Lightning Arrester on HV connected to transmission line. How to get proper spec of arrester for this transformer (theory, calculation, standars, etc). Also the LA is connected with discharge counter(?) what is the function of...
  15. eskim

    Generator Reverse Power Protection

    Thank you for your responses. Actually, we often have Rev. Pwr trip caused our loads are very dynamic (SHOVELS) and other big motors. Also our 9 diesel engines are same location with 4 (120MW's) steam turbines which have slow response for any load reduction. Diesel operator is little bit...
  16. eskim

    Generator Reverse Power Protection

    All, Our 5,1128 MW's diesel engines have Reverse Power Prot. setting of 0.04 x Rated MW, it used both to stop the diesel engine and open main circuit breaker. Can I just open the circuit breaker not stopping diesel engine ? Could you please explain me of the following scenario: * With existing...
  17. eskim

    150KV Line Voltage Drop

    Dear All, My friend has problem on 150KV trasmission line about 100km's voltage drop to 120-130KV. The qustion: - What is the main cause of this problem usually..all of lead, tower and distance are under rating - Is there any technic of installing capacitors to correct the voltage drop on HV...
  18. eskim

    Wood Partition at 33kV Substation

    Dear All, I just found out that on one of our Substation has wood partition to seperate Switchgears and fiber optic junction boxes. Is there any regulation about this, because in my opinion this is a fire hazard. If some one out there could advise me the regulation i would be glad and...