Hi,
1. Not used Ethernet/IP myself.
2. No problems experienced with radio band - supplier carried out a frequency scan to determine how busy. Installation is on a large Chemical site with lots of large structures and other radio systems.
3. Largest distance is 1320 metres.
4. I have copied the...
I have completed a number of projects using SLC5/03 with various radio telemetry types. Most recent comprised 3 SLC5/03 Outstations communicating with a Master SLC5/03 via DF1 protocol at 9600bps using radio modems. Data was volumetric flow, totalised flow and discrete digital signals.
The...