Thanks Quark,
So if my chiller is sized for the simultaneous peak load, and corresponding flowrate at dT of 6 deg C the primary flowrate will be less than the secondary.
This will mean that the secondary return will mix with the secondary flow (via a low loss header that is installed) this...
its a refurb of an existing.
2 port valves, variable flow no problem I agree, but not what I have here.
Are you saying the pumped flow should be sized for the sum of room peaks?
appreciate the help
Thanks, Maybe my question was not so clear......
How do I commission an individual FCU for the peak room load using a constant volume system which has a flowrate for teh simultaneous peak load?
For example I will not be able to commission each FCu for 1 l/s if the flowrate available from the...
Hi, this should be an obvious one but am not thinking it through correctly....
sticking to cooling only for the question (decoupled primary/secondary system);
I have a 4 pipe fan coil system.
I know the FCUs will be sized on room peak which will give me a CHW flowrate through the FCU (lets...
Are there any standards, codes, guidance notes available for the design of enclosure over pressure relief on fire suppression systems (oxygen displacment). UK preferred.