Thanks...no problem. I think I just sorted it out. The person that told me about combining circuits of like phases was referring to a 208 VAC circuit. That is when you need to combine like phases as you mentioned. I also have a 120VAC and 277VAC lighting circuits. In these cases...
advidana,
Let me clarify:
Breaker 1 phase A is 4 amps.
Breaker 3 phase B is 8 amps.
Breaker 5 phase C is 15 amps.
These are 20 amp breakers.
All I want to do is remove the wires from 1 and 3, tie together and use breaker 1 to supply these two circuits. Breaker 3 is then blank. What is wrong with...
I need to install an autotransformer lighting controller for a 120 VAC, 208 VAC and 277 VAC lighting circuits. Each controller will handle a 16 amp measured load which means I can combine circuits to a max of 16 amps. In each panel there is a common neutral for 3 hot feeds. I was told that on a...