  1. alce

    Delta-Wye transformers: zero sequence effects

    The only way the saturation in the core could have any influence on the voltage waveform is if the iron reluctance excess the reluctance of the air path. For zero sequence current "the total flux through air will be the summation of the three individual equal fluxes in the three...
  2. alce

    Delta-Wye transformers: zero sequence effects

    Yes, both transformers are dry-type. Saturation could case the voltage dip. However, the recorded voltage magnitude is only 10 volts peak. I think the voltage is too small to have saturating iron.
  3. alce

    Delta-Wye transformers: zero sequence effects

    The goal of the test it to determine the effects of a zero sequence current component on the voltage. The reason is that we want to use capacitor banks to compensate undervoltage conditions. We would like to know if we should control the phases independenly or together ( only positive sequence)...
  4. alce

    Delta-Wye transformers: zero sequence effects

    When the flux closes through the air there is a very small saturation (it behaves as an air-gap inductor). Besides, the voltage measured at the wye terminal is very small. Therefore, saturation is out place. The question is, what causes the voltage distorsion. Should the distorsion be realted...
  5. alce

    Delta-Wye transformers: zero sequence effects

    -We haven't followed any standard - The zero sequence current flows in a delta winding, and it does it within the windings when the loop is closed. By the way, in all our test the delta side was unloaded - Is doesn't matter is Wye was grounded or not. The zero current source was connected...
  6. alce

    Delta-Wye transformers: zero sequence effects

    We have carried out two tests on a three-phase delta-wye 3-legged core transformer, to see the effect of a zero sequence current on the transformer voltage. A).- System conditions for test 1 - Delta open ( we open one of the phases) so the zero current can not flow. -We supply the wye side...
  7. alce

    Transformer test

    We have a three distribuiton transformer (1MVA 12.47kV/480V), and we would like to run different test to calculate the following capacitances: - Phase to Phase - Primary to secondary - Phase to ground. I was wondering if anybody knows of any technique/procedure or circuit configuration that...
  8. alce

    High frequency transformer model

    I am studying the impact of vacuum circuit breakers on distribution transformers with different load types. I was wondering if anybody knows where I can get the parameters ( the actual RLC values and equivalent circuit) of a three-phase 1MVA transformer model(12.47kV-480v, delta-wye connected)...