  1. shirui

    Line Diferential Relay l-90 doubt

    I agree with alehman, 1ms asymmetry in communication will cause 1x360/50=18 degree difference in phase angle.
  2. shirui

    Grounding Bank

    Ground transformer is used to provide a source of ground fault current during line to ground faults, limit the magnitude of transient overvoltage when restriking ground fault occurs and permit the connection of phase to neutral load. There are several type of ground transformer such as Zig-zag...
  3. shirui

    HV Circuit Breaker Spec: Shunt Reactor Switching Application

    It seems to me that magnitude of the transient recovery voltage (TRV) and/or rate of rise of recovery voltage (RRRV) exceed the breakers's capability. My 1. Generally speaking it is ok but in your case, You should do simulation to check TRV and RRRV of these breakers. Does the breaker fail on...
  4. shirui

    programe for flexible conductor tension calculation

    jghrist and saltan, your information are very helpful for me. Thank you very much!
  5. shirui

    programe for flexible conductor tension calculation

    I am looking for standards or programs for flexible conductor tension calculation in substations. Any comments will be appreciated. Thanks