u have not mentioned the motor winding connection, feeder rating should be capable of drawing the starting current, the motor no load current will be as observed in many such practical cases is about 20-25% of FLC.
as if the voltage drop is not above limits, please also check for short circuit at motor terminal in view of cable short circuit capacity, i have no idea about any sta--ry requirement.
thanks