  1. hinrg

    Power Distribution Unit problem

    mpparent, sorry about the improper response, i wasn't paying attention to details.
  2. hinrg

    Power Distribution Unit problem

    mpparent; Did you check the voltage inputs to the static switch? Are they an A / B input from two seperate UPS systems or are they a UPS / utility fed. it sounds like you were on sub "A" one time and sub " B" on the other. Also, what type of meter are you using. The PDU...
  3. hinrg

    Parallel Generator Solid Ground Circ Current

    KBA, Have you reviewed the use of cross current compensation CT's. The output of these devices will feed directly into the AVRs. This will help in regulating the droop and voltage outputs of the machines, thus reducing the circulating currents.