Search results for query: *

  1. Rustyowls

    Condensate Drain Trap!

    I checked out the video...this is indeed very cool. I will contact them and find out. My only concearn is the demonstration is against 2" of negative static...we're looking at 4-5" depending on filter loading. If they dont have this thing for higher static applications, they should start...
  2. Rustyowls

    Condensate Drain Trap!

    Thanks Guys....my problem is there is literally only 3 1/2-4" to work with in the vertical dimension to the floor. Then the line runs parallel to the unit out of the building. These pumps might be our only answer. My question with the pumps is do they have a large enough pumping capacity to...
  3. Rustyowls

    Condensate Drain Trap!

    Ok....we recently installed an air handling unit (14,000 cfm, approx 6.5" total static, 3.5" at the trap, draw through unit). The issue is the unit is squeezed in a basement, and couldnt be provided with a baserail. as such, we only have a 4" housekeeping pad. Obviously this wont allow for...
  4. Rustyowls

    chiller sizing help

    I would contact a manufacturer, probably York...they are still the chiller guys!