    Fuse selection for transformer inrush current

    Thanks for all the help chaps, it would appear i have made a mistake in that the transformer is not 3-phase but is connected phase to phase, so is 400V but the 1.73 is not needed in the calc. JGhrist seems to be on track i think with the fact that i will need to integrate the area below the...
  2. Jeffduk

    Fuse selection for transformer inrush current

    The primary voltage is 400V 3 phase the 5x full load current refers to the manufacturers rating of a maximum inrush current of 5 x the full load capable of the transformer. full load is approximately 320A therefore 5 x is 1600A. you then square this number and multiply by 0.1 secs. my...
  3. Jeffduk

    Fuse selection for transformer inrush current

    Hi new to this forum, but it looks very helpful. my question is this: I am trying to select an REC Cut-out fuse (BS88) that will not rupture whilst powering up a 125kVA transformer. The inrush rating given by the manufacturer is 5 times full load current. i understand that whilst looking...