  1. pk786

    Free pipe sizing program

    hi find difficult to open
  2. pk786

    Cooling Tower plume formation

    IGORV2 your Q is not clear are u talking about the Fan blades of cooling tower.
  3. pk786

    RETURN LOCATION

    i think your plant is under size you have to do insulation or cealing relocat the supply and returen grillwhat typr of insulation on duct for supply and returen check your door and windows for out door air leak.Also check your steel roof for out door air leak.make your room air tight you will...
  4. pk786

    absorption chiller performence

    hi Quark thanks for your repply.Manufacture is going to vist the site next week.if you plz give me your E mail i will send you log sheet.
  5. pk786

    absorption chiller performence

    Hi Quark thank u for ur repply cooling water temp is 32C in and out from abs 37C. fouling in heat exch i did not under stand.there is auto decrystallization in chiller.Delta P cooling water is 88kpa and chilled water delta P is 47kpa.natrual Gas pressure is 200mmqa.vacum is ok now pleas advice...
  6. pk786

    absorption chiller performence

    Hi all i want to aske about delta t of my abs chiller delta t is only 2c chiller is 330 ton of ref.i want to to the reson pleas help me.