  1. kh2

    Transmission line voltage level

    The following information is about the surge impedance loading or SIL (in MW). The Surge Impedance Loading (SIL) of a transmission line is the MW loading of a transmission line at which a natural reactive power balance occurs. The concept of SIL is explained as follows: 1) Transmission lines...
  2. kh2

    Generator Circuit Breakers

    ScottyUk, Thanks for your comments. I think that the generator circuit breaker is preferable in power plants with large units. There is no argument that there are cases the GCB is not cost effective. Agree that GCB is not a requirement. When I responded to the question, I had in mind the...
  3. kh2

    Generator Circuit Breakers

    We may start by saying that the major objective of operating a power plant is to achieve the highest possible plant availability at the lowest possible cost. The use of a generator circuit breaker (GCB) could achieve this goal because of the following advantages: 1) Installation of the GCB...
  4. kh2

    Busbar Clearances

    You may consider the minimum clearances given on the National Electrical Code (NEC) table 490-24. This table provides the phase-to-phase and phase-to-ground minimum clearances of live parts for indoor and outdoor applications. For example the clearance for 7.2 kV ph-grnd is 4.0 inches and for...
  5. kh2

    The determination of the number of slots in a synchronous generator

    Edison 123, You are right. Last communication was in 2004. Another thread that interested you was the clearance between the coil/bar end turns. But I follow your discussions and learn a lot. Zlatkodo attachment is super. Best regards, kh2
  6. kh2

    The determination of the number of slots in a synchronous generator

    Edison 123, Good to hear from you. Appreciate very much your valuable recommendation. Thank you.
  7. kh2

    The determination of the number of slots in a synchronous generator

    Thank you greatly for the correction and the formula. This means to use one turn/coil (roebel bar) and 2 circuits will result in doubling the number of slots. I thought that substituting two turns/coil with one turn/coil of a cross section equal to the two turns, will keep the number of...
  8. kh2

    The determination of the number of slots in a synchronous generator

    Thanks again. The existing machine slots/pole/phase =2.75 and the grouping is 3.3.3.2/3.3.3.2/3.3.3.2 repeated 6 times. Coil sides per slot is 2. If we used C1 = 198 slots; TPC1 = 2 & TPC2 = 1; N1 =2 & [N2= 1 or 2 or 3] Therefore C2 = [C1x(TPC1)x(N1)]/[(TCP2)x(N2)] C2 (for one circuit and one...
  9. kh2

    The determination of the number of slots in a synchronous generator

    Thanks for your response. If we decided to rewind using one turn per coil (roebel bars) and 3 circuits/phase, then we will have: T2 =1, T1 =2, N1 =2, and N2 = 3. Then we apply T2/T1 = N2/N1, the result will be 1/2 = 3/2. This is an incorrect equation, and where it shows that the number of the...
  10. kh2

    The determination of the number of slots in a synchronous generator

    The project is to upgrade a hydro synchronous generator 50 MVA, 24 poles, 3-phase wye, 13.8 kV L-L, lap winding, 2-turn/coil, 2-circuits, 198 slots. The upgrade shall include the rewind and to replace the stator core. The new rating shall be 60 MVA. The alternatives for the rewind are one turn...
  11. kh2

    Calculating transformer fault currents HI/LO side

    To solve this problem you have to know the utility (source) 3-phase fault current or MVA. Assume that the source 3-phase fault is 2500 MVA. Then use the transformer MVA as the MVA base. 1) Source (utility) p.u. impedance = MVA base/SC MVA source = 20/2500 = 0.008. 2) Transformer p.u. impedance =...
  12. kh2

    Motor Theory Book

    Also, you may consider a good reference book called "Electric Machinery and Transformers" by Irving L. Kosow. On Chapter 9 and 10, the author provided an easy to follow, supported by questions and answers, the principles, characteristics, and construction of polyphase and single phase induction...
  13. kh2

    Unit main transformer sizing?

    Elep, I came across your post late, but felt that you may look at IEEE C57.116-1989 since your original question was about standards/references. It is called IEEE guide for transformers directly connected to generators. The guide describes the selection of Unit Transformers and Unit Auxiliaries...
  14. kh2

    Max LG Fault Current on Autotransformer

    Agree with all you wrote saladhawks. My original question to zhz was related to the formula that he used to calculate the LV side fault. I was trying to understand how the formula was developed. I am familiar with a simple approach which gives the same result as follows: 1) Use MVA base = 1MVA...
  15. kh2

    Max LG Fault Current on Autotransformer

    Hi zkz, Please note the following correction to my last calculation of 926 amps for the fault current on the secondary side of the 1000 kVA, 24.94/12.47 kV( L-L), 3-phase, 5% Z, auto transformer: The 926 amps is 1.37 times the 674 amps that dimartin obtained, and is 1.17 the 791 amps that you...
  16. kh2

    Max LG Fault Current on Autotransformer

    Hi zkz, Thank you for your response. If the transformer impedance is the only impedance to calculate the transformer LV side fault current, it will be = I(secondary)/per unit impedance = 46.3/.05 =926 Amps. This value is 0.727 of the value that dimartin obtained and is 0.85 of the value you...
  17. kh2

    Max LG Fault Current on Autotransformer

    Hi zkz, Please explain the formula you used to calculate the low voltage (LV) side MVA fault level. Which is given as = " HV side MVA / (1+(HV side MVA/1)*per unit impedance". Why did not use the available HV side fault current to calculate the LV side fault current? Thank you, Kh2
  18. kh2

    What is the min. striking distance between energized parts and covers?

    Thank you PWR and edison 123 for your responses. NEC Article 49 is addressing bare conductors. Our case is about a fully insulated conductor. I was told that the striking distance for 13.8 kV insulated stator bars has to be 2.5" regarless of the material of the covers (metal or fiber glass)...
  19. kh2

    What is the min. striking distance between energized parts and covers?

    This question came up during the rewind of a 13.8 kV machine 40 MVA, Hydro. The new bars were elongated by about 6 inches. As a result the air baffles (covers) became closer to the overhang portion of the bars which reduced the clearance between the live parts and the covers. The Contractor...
  20. kh2

    What is the min striking distance for a 13.8 kV generator winding?

    In the rewinding and uprate of a 40 MVA (uprate to 46 MVA), 13.8 kV, 3-phase, 60 hz, one circuit, wave winding, hydro generator, the mean length turn has increased to achieve bar end arm and cross over clearances of 1/2". This resulted that the overhang portion of the bars (winding) was...