To quark,
Yes, the valves will close off from time to time, some more than others as some are oversized because they changed the partiiton layout so some units have a much smaller area to cool than previously. I have not beem able to do it yet, but I plan to increase the water supply temp. to...
SAK 9, I think you may be right. There is no option to install reheat, but the water supply temp could be increased a bit to increase the temperature off the coils.
We have reduced the fan speed (3 speed control) and the condensation is not nearlly as bad, but still present.
The outside air...
I have a problem I have never encountered before.
A chilled water system with a series of fan coils. Each fan coil is installed in a bulkhead with a short section of supply duct terminating in a sidewall grille. We are getting condnesation on some of the grilles. Has anyone ever experienced...