    950kVA Generator cannot pick up load

    Using a generator sizing program, a 160 KW block load with across-the-line start and allowing only a 15% voltage dip; indicates a genset requiremet of 1100 KW. You didn't indicate if yours is diesel or natural gas. If gas,motor starting capabilities are even worse. I would try reduced voltage...