  1. Reactorman

    Fault Current Electromagnetic Forces

    The Web site below has formula's to calculate these forces. Good luck http://www.cda.org.uk/megab2/elecapps/pub22/sec6.htm#Electromagnetic%20Stresses
  2. Reactorman

    Power transformer - allowable winding temperatures

    The transformer at 160 deg C hot spot is only 3- 4% above the Max. limit. This should not cause breakdown. Also since this only occurs at 35 deg C ambient there may not be a significant loss of life. However you might consider adding fans to be on the safe side. Good Luck
  3. Reactorman

    reactors and capacitors

    Field tests on reactors are difficult, because if you apply full voltage the reactor will be at full power You can measure resistance, and since the reactor is probably linear you could apply a low voltage across the reactor and read the current. There are also bridges available that can...
  4. Reactorman

    De-magnetizing a Transformer

    Although the method I'll describe may not be practical to do. It explains a proceedure to accomplish demagnetization. "Energize the transformer no load, and then gradually reduce the voltage to zero. The core will be demagnetized." Good Luck
  5. Reactorman

    Transformer Inrush earth fault trip

    Inrush current will be at a maximium if the breaker closes on a voltage zero. Of course this can only occur on one of the phases since the other two phases cannot be also on a voltage zero. The book "Transformer Engineering" by Blume includes a formula for this calculation, however you would...
  6. Reactorman

    DC Current Transformers

    I know Seiman's made some back in the 80's. We also made some in the Company i worked for but only for in house use not for sale outside. The DC primary current saturates the core, so the secondary has an AC voltage applied to unsaturate the core every cycle, This is an over simplfied...
  7. Reactorman

    Determining The Required Inductance for an AC Line Reactor

    I have not done this, but if I understand the problem this should work. 1) calculate the capacitance above .125uf 2)calculate the Ohms of the above capacitance. 1/2xPIxFxC 3) The above is the required reactor ohms at the rated frequency. Reactorman
  8. Reactorman

    Power transformer inrush current

    The main factors which determine transformer inrush current are as follows: 1)The residual magnetism in the core this will vary from zero to approximately 70% depending mainly on the instantaneous value of the voltage when the previous shutdown occured (this does not happen in a motor as the...