One of your reply indicates yu are using,Transformer 13.8kV to 600V, 1MVA,
The general requirement is to check the touch & step potential if the equipment is in the open switch yard.
For low voltage system there is no need to check for touch & step pots.
You have to define the duration of 50kA...