I concur with DPC; ETAP software uses IEEE1584 equations to calculate arcing fault current and incident energy for les than 15KV systems. In those equations arcing fault current equation included short circuit current as a major factor in the calculation and incident energy equation included arc...
we specified the use of 220VAC for motors loacal control panel which will contain mainly start/stop push bottoms.
some of the motors will be 225 meter away from MCC, we are using 2.5mm2 cable(#14 AWG)three conductor cable for that.
my question is: due to the long distance is it possible that the...