What is your occupation?
There are to many variables to get an answer here.
You have to figure fire flow for the building, water supply either public or tank or other, fire sprinkler system demand. Not sure why a standpipe is involved.
Interesting. I do agree a yearly pump test is required/ needed
But to do it just for adding to the system?
Maybe depends on what you will be trying to protect?
Interesting question
To design a sprinklers system???
Or other??
I am not a designer or engineer,,, but have never seen a pump test submitted for a sprinkler flow test design?
Anyway easier to do a fire hydrant test
Hire a sprinkler company to do it
7. The plant’s two diesel engine driven fire pumps failed, at 30 minutes and 45 minutes into the fire, making the two independent on-site backup water supplies essentially useless. The USFA investigator was not permitted to enter the pump house, but the pump failures were believed to be due to...
The systems I have seen ,,,
1. Automatically dump upon detection
2. By manual pull station
The only interrupt I have seen is
1. A manual abort, which is a dead man switch. Someone has to stand there and hold it. Once released the count down continues.
2. Keyed switches, to override the...
Not an engineer or even close, plus, been forever since I have seen indoor flammable storage
Looking at NFPA 30 2024
Appears, depends on what you are dealing with, as far as design
I guess you have seen 16.8.1 and 16.8.2 is one example, appears you design to the design area of the sprinkler...