Yes the problem is leading power factor. Due to 10 kV and 60 kV cable. There is also voltage regulation problem, the problem is that the voltage rises to much.
Therefore we have to reduce the production of reactive power or consume some reactive power.
I have heard that i Germany the have...
Due to new regulations from the Danish transmission accountable (400 / 150 kV), we in the distribution (60 / 10 / 0,4 kV) companies have to ensure that the reactive flow thou the 150 / 60 kV transformer is within defined MVAr limits.
The one side of the problem will resolve it selves, when the...