thank you. I will find out what my clients line size is going to be. I will also check on the chloride issue. that is what made me concerned about 304 in the first place. May have them consider CPVC but this piping run has some potential support limitations which could be problematic.
I have read the stainless and sulfuric acid posts and looked at the references out of them.
The charts and articles I have found seem vague at these low concentrations. In your opinions is 304L SS piping acceptable in a 0.04wt% sulfuric acid stream at 120 deg F? Are there any specific...
We purchased a used boiler that came with both a stop check valve and a stop valve. We are going to install as the only boiler in the system and no other steam sources attached to the header. When reviewing ASME B31.1 - 2004 section 122.1.7 (A) specifically(A.3) it would appear that a stop...
What if my shut off valves are also rated above the supply line pressure.
Is there some code about relief valves being needed to limit the potential gas flow to a burner if the high gas pressure switch failed at the same time as the gas regulator?
I have conflicting information on the requirment for a Pressure Safety Relief valve on the natural gas supply line after the regulator and before the automatic fuel shut off valves. Does anyone know which code lists that requirment?
The piping between the reducing valve and the burner is...