I try and calculate fault current on a system coonsisting for example a generator and line and I have basic parameters. For the generator I thought the subtransient reactance would be enough but alas! When I try now to use a Power system analysis package, it asks me for all kind of things, Xd...
Very interesting info from you guys. I considered a fault at generator terminals with X1=0.3, x2=.2 and x0=.1 then I found SLG=5 pu and 3phase symmetrical fault=3.33 pu. If I change x0 to 0.5 then SLG = 3pu. It seems that for low x0, SLG faults are worse than 3 ph bolted faults.
Comments?