Hi Steve
Overload protection in YD setups
You say you have a 4kW motor, I guess approx 7.5Amps FLA
Overload protection can be applied to this setup in three ways:
a) If you have a motor protective breaker in the three phases upstream of the main contactor then you would set the overload of...