1.I checked the March Pumps from the web site.Series 5.5 seems to be too high( 40 feet head) and Series 5 seems to be insufficient( 28 feet head)as we have to limit the system to be below 15 psig due to local regulations.Any otther suggestions/vendors?
The pump will be...
Hi
Thanks for your response.This is an existing tank and nothing can be done about it.As mentioned earlier this tank needs preferably to be kept water free so that there is no potential of leakage into the adjacent area.
We have an atmospheric pressure underground tank 8ft L X 14 inches W X 3 ft-4 inches deep ( 233 US gal capacity) .The bottom of this tank is 21 feet below the ground level. Water is seeping into this tank from surroundings at the rate of 0.3 gpm. It is a requirement that this tank should be...