  1. IncogNico

    Hot Water Tank with 2 Pumps and H.Ex.

    If the system is already installed to get accurate results I would install a thermostat at the output. This way you can read the temperature through all of its stages. I am sure that you will find that it will never be constant and will always be fluctuating. Unfortunately unless I spend a lot...
  2. IncogNico

    Hot Water Tank with 2 Pumps and H.Ex.

    To be able to maintain a “relative” temperature of 106ºF as the output you must have at least 2558 lb/hr which will be a total HX duty of approx 2,250 MBTU/hr. Once the recalculating pump kicks in, assuming the Steam flow above, the max output temperature that you could achieve would be approx...
  3. IncogNico

    Hot Water Tank with 2 Pumps and H.Ex.

    enenenen, To be able to help you out without a lot of back and forth, all I need are your specifications. by the sounds of it you have a storage tank and a heat exchanger. all i need are the conditions of the heat exchanger loop and the domestic. Hot Side: 110 Psi Steam (approx. 344ºF)...