If the system is already installed to get accurate results I would install a thermostat at the output. This way you can read the temperature through all of its stages. I am sure that you will find that it will never be constant and will always be fluctuating.
Unfortunately unless I spend a lot...
To be able to maintain a “relative” temperature of 106ºF as the output you must have at least 2558 lb/hr which will be a total HX duty of approx 2,250 MBTU/hr.
Once the recalculating pump kicks in, assuming the Steam flow above, the max output temperature that you could achieve would be approx...
enenenen,
To be able to help you out without a lot of back and forth,
all I need are your specifications.
by the sounds of it you have a storage tank and a heat exchanger. all i need are the conditions of the heat exchanger loop and the domestic.
Hot Side:
110 Psi Steam
(approx. 344ºF)...