  1. dana1028

    Primary/Secondary Current or Voltage

    "Sure there are, the ASHRAE 90.1 energy code includes maximum permissible voltage drop requirements. ASHRAE 90.1 has been adopted by most US jurisdictions." Thank you for the reply...however - 1. ASHRAE is not a code...it is a standard 2. US jurisdictions typically do not adopt standards...to...
  2. dana1028

    Primary/Secondary Current or Voltage

    "To comply with the code required 3% or 5% maximum voltage drop." Just a minutia comment - there are no code requirements to limit voltage drop. The code has Fine Print Notes [which are not enforceable] which 'suggest' sizing conductors to limit voltage drop in branch circuits and feeder...