Eng-Tips is the largest engineering community on the Internet

Intelligent Work Forums for Engineering Professionals

  • Congratulations waross on being selected by the Tek-Tips community for having the most helpful posts in the forums last week. Way to Go!

Search results for query: *

  1. jb17136

    Poloraziation Index

    To electricpete Yes I go to LEMUG, are you going in August? I think we are dancing around the whole PI issue here. Hypress was looking for a good PI acceptance number for a new, unused motor. The ones he tested seemed to be high. Moisture seemed to be a possibility, especially for a modern...
  2. jb17136

    Poloraziation Index

    To Electricpete. I would agree that suspecting moisture due to a high PI for a modern winding would be a departure except the initial conditions were: new motors, never in service. I assumed storage of some kind, and while dirt, contamination, and deterioration and other normal enemies of...
  3. jb17136

    Poloraziation Index

    I agree with utvol, the PdMA tester is a good tool. My first question would be what is the resistance to ground and how quickly does it get there. If the resistance to ground exceeds 5 gigohms in the first minute and stays there througought the 10 minute test with a good smooth curve, then the...