I witnessed a situation years ago - two of the leads (A and C) in a 10 MW machine were inadvertently swapped while replacing the 4.16 kV terminal cables. Two attempts were made to close the synchronizing breaker, causing the generator differential relay to trip instantaneously in each attempt...