Could someone help clarify a code issue with me ?
In a large institution like a High School, if one were to add a small (~400 cfm) range hood, what kind of mechanical interlocks between the exhaust and supply would be required to satisfy building code? Would you have to ensure that the main air...
Hi,
Can anyone explain what value to use for the maximum pressure, when sizing an expansion tank. This is on a closed secondary loop. If it were the primary side it would be determined by the boiler PRV, but what is the determining factor for a secondary loop with a water to glycol heat...
I agree. I just found out that there was a roof top unit with a glycol coil installed on the roof along with the new expansion tank. The spec called for a 12 psi pre-charge which would be way too low since the RTU is 3 stories above...would you agree?
One more question. The proper maximum...
BTW
3782 U.S. gallons (50/50 mix) is the closed system volume.
Diaphragm tanks are 264 U.S. gallons each (quantity of 2) for a total of 528 U.S. gallons. 12 psi precharge and acceptance volume is 81% of tank volume.
We have a school with a primary heating loop off the boilers and a secondary glycol loop via a converter. Our plumbers are telling me that in the shoulder seasons when the temperatures are warmer they have to add fluid beacause the pressures in the glycol side are too low but when the outdoor...