I'm working in Guinea for an NGO troubleshooting a power problem. The office where I'm working has a 3-phase 30kVA SDMO generator. They are overlaoding it (mainly with AC units). RIght now I'm trying to balance the load but its all in an effort to reduce the blinking lights, beeping UPS's...
I seem to have had some bad info there. The regulators do not consume their full amount of power. So we're gonna have to make some bigger cuts else where or figure out a way to ration the power out.
I'm now at the site. After listening to the engine and looking git over I started running down what was plugged in where and doing a little math. Based on my calculations (which are incomplete as I don't have the exact V A or W rating for everything so I'm ballparking it) they are trying to...
Hello,
I'm working with an NGO in Guinea. There is an SDMO J30 (30KVa 1500 rpm, John Deere Engine with a Makalte Alt.) unit at an office up country. I have a lot of troubleshooting experience with gas engines but little with Diesel engines. I've yet to see it but I'm headed out this...